Range Hood Sizing: Width, CFM, Duct Size and Mounting Height

Updated November 19, 2026

A range hood removes heat, steam, grease and cooking odors, and with a gas range it also removes combustion byproducts. Its performance depends on four things: how well it covers the cooking surface, how much air it moves, how freely that air can leave through the duct, and whether the house can replace the air that is removed.

This guide explains the usual rules of thumb for each. They are estimates. The hood and range installation instructions and the local mechanical code set the actual requirements, and a new or enlarged duct through a wall or roof often needs a permit.

Ducted and recirculating hoods

A ducted hood exhausts air to the outdoors. It removes heat, moisture and combustion gases as well as grease and odor, and it is the better choice wherever a duct route exists.

A recirculating, or ductless, hood pulls air through a grease filter and a charcoal filter and returns it to the room. It reduces grease and some odor but does not remove heat or moisture. Charcoal filters need replacing every few months with regular cooking. Recirculating hoods are used where a duct is not practical, such as in some apartments and interior walls.

Over-the-range microwaves include a small fan and can usually be set up either way. Their capture area is shallow, so they are less effective than a dedicated hood of the same airflow.

Hood width and depth

The hood should be at least as wide as the cooking surface. A 30-inch range takes a 30-inch hood at minimum. A hood 3 inches wider on each side captures more, and this extra width is commonly recommended for island hoods and for high-output ranges.

Depth matters as much as width. A hood should cover the rear burners fully and at least half of the front burners. Wall hoods are typically 18 to 22 inches deep, and deeper models of 24 to 27 inches are made for professional-style ranges. Island hoods have no wall to help contain the plume, so they benefit from being larger and are usually mounted a little lower within the allowed range.

Estimating airflow in CFM

Airflow is rated in cubic feet per minute, or CFM. Common rules of thumb give a starting point:

Cooking surfaceRule of thumbExample
Gas range or cooktopAbout 100 CFM per 10,000 BTU of total burner outputA 50,000 BTU range: about 500 CFM
Electric or induction, wall hoodAbout 100 CFM per linear foot of range widthA 30-inch range: about 250 CFM
Electric or induction, island hoodAbout 150 CFM per linear foot of range widthA 30-inch cooktop: about 375 CFM
Typical residential 30-inch range, ordinary cooking250 to 400 CFMMost standard kitchens
Professional-style 36 to 48 inch gas range600 to 1,200 CFMFollow the range maker's hood guidance

The gas rule assumes every burner on high at once, which is rare in home cooking, so it tends to overstate the need for ordinary ranges. More airflow is not automatically better. Larger fans are louder, need larger ducts and may trigger makeup air requirements. A hood that fully covers the burners with moderate airflow usually outperforms a small hood with a powerful fan.

Duct size and routing

The duct determines how much of the rated airflow the hood actually delivers. An undersized or long, winding duct reduces airflow and increases noise.

  • Up to about 400 CFM: usually a 6-inch round duct, or a 3.25 by 10 inch rectangular duct
  • About 400 to 600 CFM: usually a 7 or 8 inch round duct
  • About 600 to 900 CFM: usually an 8 inch round duct
  • About 900 to 1,200 CFM: usually a 10 inch round duct
  • Material: smooth-wall rigid metal duct. Flexible plastic or foil duct is not suitable for range hoods.
  • Route: as short and straight as possible, with few elbows. Each 90-degree elbow adds resistance equal to several feet of straight duct.
  • Termination: outdoors through a wall or roof cap with a backdraft damper. A range hood must not exhaust into an attic, crawl space or garage.

Never reduce the duct below the size of the hood's outlet. The manufacturer's instructions give the maximum duct length for each duct size.

Mounting height above the cooktop

Most hoods are installed with the bottom edge 24 to 30 inches above an electric cooktop and 24 to 36 inches above a gas cooktop. The hood manufacturer states an allowed range, and the range manufacturer states a minimum clearance to combustible surfaces above. Both must be met.

Mounting higher than recommended lets the cooking plume spread past the hood edges. Mounting lower than the minimum can be a fire hazard and can block the view of the rear burners. Tall users sometimes prefer the upper end of the range, and a wider or deeper hood helps compensate for the extra height.

Noise and makeup air

Hood noise is rated in sones. Lower is quieter. Around 1 to 3 sones at low speed is quiet enough for conversation, and many hoods reach 6 to 9 sones at full speed. A hood that is too loud tends not to be used, so compare the ratings at the speed likely to be used most. Larger ducts, fewer elbows and remote or inline blowers reduce noise.

A powerful hood removes more air than a tightly built house can replace through leaks. The resulting negative pressure can pull exhaust gases back down the flue of a gas water heater, furnace or fireplace. Many building codes require a makeup air system when a kitchen exhaust hood is rated above 400 CFM, with details that vary by jurisdiction. Check with the local building department or an HVAC contractor before selecting a hood above that size.

Common range hood mistakes

  • Choosing a hood narrower than the range
  • Buying high CFM and connecting it to a small or flexible duct
  • Venting into the attic or soffit space without a proper exterior termination
  • Ignoring makeup air requirements for hoods above 400 CFM
  • Mounting the hood higher than the manufacturer allows to clear sight lines
  • Selecting on maximum airflow without checking the noise rating
  • Planning cabinets and tile before confirming the duct route through framing
  • Not cleaning grease filters, which reduces airflow and is a fire risk

Frequently asked questions

How many CFM does a range hood need?

For a standard 30-inch electric or induction range, 250 to 400 CFM is typical. For gas, a common estimate is 100 CFM per 10,000 BTU of total burner output. Good coverage of the burners and a properly sized duct matter as much as the CFM rating.

Should a range hood be wider than the range?

It should be at least the same width. A hood about 6 inches wider than the cooking surface captures more and is commonly recommended for island installations and high-output gas ranges, if the cabinet layout allows it.

Is a ductless range hood worth installing?

It is better than no hood. It traps grease and reduces some odor, but it does not remove heat, moisture or combustion gases. Where a duct to the outdoors is possible, a ducted hood performs much better.

How high should a range hood be above the stove?

Typically 24 to 30 inches above an electric cooktop and 24 to 36 inches above a gas cooktop. The exact range comes from the hood's installation instructions, and the range's minimum clearance to combustibles also applies.

When is makeup air required for a range hood?

Many US codes require makeup air when a kitchen exhaust hood can move more than 400 CFM, in some cases only when the home has fuel-burning appliances that could backdraft. The rule depends on the code adopted locally, so confirm it with the building department.